Protection of circuits against short-circuit currents, protection of circuits against overload currents switch, isolation.
EBS7B circuit-breakers are used in domestic installation as well as incommercial and industry electrical distribution systems.
Technical data of the network at the point considered: short-circuit current at the circuit-breaker installation point, which must always be less than the breaking capacity of this device, network normal voltage.
Tripping curves:
B curve (3-5In)
Protection for people and big length cables in TN and ITsystems.
C curve (5-10In)
Protection for resistive and inductive loads with low inrushcurrent.
D curve(10-20In)
Protection for circuits which supply loads with high inrushcurrent at the circuit closing(LV/LV transformers, breakdown lamps)
Approvals and certificates CE, CB
| Standard | IEC/EN60898-1 | ||||
| Model | EBS7B-63S | EBS7B-63N | EBS7B-63H | ||
| Rated current In | A | 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63 | |||
| Rated voltage Ue | V | 230/240V (1P+N), 240/415V (1P), 400/415V (2P/3P/3P+N/4P) | |||
| Rated frequency | Hz | 50/60Hz | |||
| Poles | P | 1, 2, 3, 4, 1P+N, 3P+N | |||
| Mechanical life | 20000 | ||||
| Electrical life | 10000 | ||||
| Rated short-circuit breaking capacity Icn | A | 4500 | 6000 | 10000 | |
| Operating short-circuit breaking capacity Ics | A | 4500 | 6000 | 7500 | |
| Rated insulation voltage Ui | V | 500 | |||
| Rated impulse withstand voltage(1.2/50)Uimp | kV | 6.2 | |||
| Dielectric test voltage | V | 2000V (50Hz, 1 minute) | |||
| Vibration resistance(IEC/EN 60068-2-6) | No obvious vibration and impact | ||||
| Terminal Blocks | Minimum connectable conductor cross-sectional area (mm²) | 1.5 | |||
| Maximum connectable conductor cross-sectional area (mm²) | 25 | ||||
| Standard connection torque (N·m) | 2-2.5 | ||||
| Maximum withstand torque (N·m) | 2.5 | ||||
| Conductor insertion depth (mm) | 10-15 | ||||
| Reference Temperature | °C | 30 | |||
| Operating Temperature | °C | -25~+40 | |||
| Storage Temperature | °C | -35~+85 | |||
| Applicable Altitude | m | ≤2000 | |||
| Trip Type | Thermal magnetic tripping | ||||
| Instantaneous trip type | Type B (3In~5In) | · | |||
| Type C (5In~10In) | · | ||||
| Type D (10In~20In) | · | ||||
| Cable Entry | Both up and down | ||||
| Installation Method | TH35-7.5 standard guide rail | ||||
| Pollution Degree | 2 | ||||
| Protection level | Direct installation | IP20 | |||
| Install in the distribution box | IP40 | ||||
| Accessories | OF, SD, MX, MN, MV+MN, OF+SD | ||||

Residential Buildings · Commercial Buildings · Industrial Facilities · Distribution Panels · Lighting Circuits · Power Distribution · Solar PV Systems
Q1: Can I get samples for testing?
Yes. Samples are available for quality and performance testing.
Q2: Do you support OEM/private labeling?
Yes. We support OEM/ODM, including private labeling and customized packaging.
Q3: What certifications are available for this model?
CE, CB, TÜV and other certifications are available depending on the model. Please contact us for details.
Q4: Can you supply different poles and tripping curves?
Yes. Different poles and B/C/D tripping curves are available depending on the model.
Q5: What is the typical production lead time?
Typically around 35 days, depending on order quantity and customization requirements.
![]() |
|||
| Quality Assurance» | View Certifications» | ||