Products
BX2MR pulse relay can realize remote control circuit: multi-point control through pulse command. pulse relay is used to control resistive load circuit (such as incandescent lamp, low-pressure halogen lamp and convection heater) and inductive load circuit (such as fluorescent tube and discharge lamp)–Standard EN 60669-2-2
Type | Standard | BX1MR-16A | ||
Control circuit |
dissipated power during impulsing time | VA | 19 | |
Pushbutton control with indicated lighting | mA | Max current 3mA | ||
working threshold | Un | Min 85% based on EN/IEC 60669-2-2 | ||
duration of control command | ms | 50ms-1s | ||
reflection time | ms | 50 | ||
Main circuit |
Rated voltage(1P 2P) | V AC | 24…250 | |
Frequency | Hz | 50/60 | ||
Max operation times per minute | 5 | |||
Max switch times per minute | ||||
Additional
features |
Insulated voltage | V AC | 440 | |
Class of pollution | 3 | |||
Rated impulse withstand voltage | Uimp | 6kV | ||
Life-span |
Electrical life | 200,000(AC21) | ||
200,000(AC22) | ||||
Over-voltage Category | IV | |||
Others |
Protection level | the device itself | IP20 | |
to install inside comsumer unit | IP40 Insulation level: II | |||
Working temperature | C | -20~+50 | ||
Saving temperature | -40~+70 | |||
Moisture and Heat Resistance | When tempeture is 55C, relative humidity will be 95% |